Fujitsu M8000 Server User Manual


 
Chapter 4 FRU Removal Preparation 4-19
2. Back up the system files and data as necessary.
3. Log into the XSCF Shell and type the poweroff command
The following activities occur when the poweroff command is used:
The Solaris OS shuts down cleanly.
The server powers off to Standby mode (the XSCF Unit and one fan will still have
power).
For details of the command, see the SPARC Enterprise
M3000/M4000/M5000/M8000/M9000 Servers XSCF User’s Guide.
4. Switch off all main line switches of the AC section.
Caution – There is an electrical hazard if the power cords are not disconnected. All
power cords must be disconnected to completely remove power from the server.
4.4.2 Powering the Server On
Two power-on procedures are available.
4.4.2.1 From the Operator Panel
Follow the power-on procedure below.
1. Confirm that the mode switch on the operator panel is set to the Service
position.
2. Confirm that the POWER LED and CHECK LED on the operator panel are off
and the XSCF LED on the operator panel is lit.
3. If the XSCF LED is off, switch on all the system main line switches.
4. Press and hold down (for less than four seconds) the POWER switch on the
operator panel.
5. Check the POWER LED.
When it becomes lit, the power-on procedure is completed.
If the state of any of the LEDs is different from the above, see Section 2.7, “LED
Error Display” on page 2-30.
XSCF> poweroff -a