Fujitsu M8000 Server User Manual


 
15-10 SPARC Enterprise M8000/M9000 Servers Service Manual June 2010
7. Connect the clip of the antistatic wrist strap and of the antistatic mat to the
server grounding port. See Section 1.4, “Antistatic Precautions” on page 1-6.
8. Ensure that the metallic underside of the wrist strap is in direct contact with
your skin. The wrist strap should be snug around the wrist so that it does not
rotate. See Section 1.4, “Antistatic Precautions” on page 1-6.
Caution – Before handling FRUs, be sure to connect the clip of the antistatic wrist
strap and of the antistatic mat to the server grounding port, and attach the band of
the wrist strap to one of your wrists. Place the FRUs on the grounded antistatic mat.
Failure to take these antistatic measures might result in serious damage.
9. Remove the tape drive unit to be replaced. (See
FIGURE 15-4 or FIGURE 15-5)
a. Using a Phillips screwdriver, loosen the two knob screws securing the tape
drive unit.
b. While grasping the knob screws, pull out the tape drive unit slowly from the
slot.
10. Place the removed tape drive unit on an antistatic mat.
11. Mount the replacement tape drive unit by following the removal instructions in
Step 9 in reverse order.
Caution – Do not forcibly push the tape drive unit in when inserting it. If the tape
drive unit is forcibly inserted despite the presence of any obstruction in a slot or any
problems with the connector pin, serious damage may result.
12. Attach the tape drive unit to the port.
Execute the cfgdevice -c attach -p <port no.> command of XSCF.
13. Confirm that the replacement tape drive unit is configured to the domain.
From XSCF, execute the cfgdevice -l command to confirm that the specified
port number is displayed in the current connection.
14. Turn on the power to the relevant domain.
From a console that is connected to XSCF, execute the poweron -d command of
XSCF.
For details of the power-on operation, see Section 4.4.2, “Powering the Server On”
on page 4-19, and the SPARC Enterprise M3000/M4000/M5000/M8000/M9000
Servers XSCF User’s Guide.
15. Start up domains as necessary.
16. Close the door on the server and lock it.