Powerware 100160 kVA Power Supply User Manual


 
15-1
EATON Powerware
®
9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com
Chapter 15 Product Specifications
15.1 Model Numbers
The UPS systems are housed in free-standing cabinets with safety shields behind the doors.
The UPS systems are available in 50/60 Hz with various output power ratings.
Models Powere Rating Frequency
Powerware 9390-120/100 100 kVA 50/60 Hz
Powerware 9390-120/120 120 kVA 50/60 Hz
Powerware 9390-160/100 100 kVA 50/60 Hz
Powerware 9390-160/120 120 kVA 50/60 Hz
Powerware 9390-160/160 160 kVA 50/60 Hz
The following sections detail the input, output, environmental, and battery specifications
for the UPS.
15.2SingleModuleSpecifications
15.2.1 UPS System Input
Operating Input Voltage
(Nominal +10/–15%)
208 Vac for operation from 177 Vac to 229 Vac
220 Vac for operation from 187 Vac to 242 Vac
480 Vac for operation from 408 Vac to 528 Vac
Operating Input
Frequency Range
¦5Hz
Operating Input Current
See Appendix A, Table E through Table G.
Reduced for Generator
Adjustable
Input Current Harmonic
Content
5% THD at full load
Power Factor
Minimum 0.99
Line Surges
6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801-4
Battery Voltage
384 Vdc (208V/220V units only)
432 Vdc
480 Vdc