Installation Information
A-25
EATON Powerware
®
9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com
Table Q. INPUT/OUTPUT Ratings for Powerware 9390---160/160 Parallel System
Configuration Units Rating 50/60 Hz
BasicUnitRatingat0.9laggingpFload
kVA
kW
160
144
160
144
Input and Bypass Input
Output
VOLTS
VOLTS
208/220
208/220
480
480
All
AC Input from UPM
Full L oad Current for each Module
(3) Phases, (1) Neutral---if required, (1) Ground
D
Amps 444/420 192
Minimum Conductor Size for each Module
NumberperPhaseforeachModule
AWG or kcmil
(each)
See Table E through
TableGforwiresize.
1+1
AC Input to Tie Cabinet Bypass (optional)
Full Load C urrent
(3) Phases, (1) Neutral---if required, (1) Ground
F
Amps 444/420 192
AC Output to Critical Load
Full L oad Current
(3) Phases, (1) Neutral---if required, (1) Ground
G
Amps 444/420 192
System Neutral Bonding Jumper
Minimum Conductor S ize
Number(See No te 27)
---
AWG or kcmil
(each)
2/0
(1)
2
(1)
2+0
and
2+1
AC Input to Tie Cabinet Bypass (optional)
Full Load C urrent
(3) Phases, (1) Neutral---if required, (1) Ground
F
Amps 888/840 384
AC Output to Critical Load
Full L oad Current
(3) Phases, (1) Neutral---if required, (1) Ground
G
Amps 888/840 384
System Neutral Bonding Jumper
Minimum Conductor S ize
Number
(See Note 27)
---
AWG or kcmil
(each)
1/0
(2)
1/0
(1)
3+0
and
3+1
AC Input to Tie Cabinet Bypass (optional)
Full Load C urrent
(3) Phases, (1) Neutral---if required, (1) Ground
F
Amps 1332/1260 576
AC Output to Critical Load
Full L oad Current
(3) Phases, (1) Neutral---if required, (1) Ground
G
Amps 1332/1260 576
System Neutral Bonding Jumper
Minimum Conductor S ize
Number(See No te 27)
---
AWG or kcmil
(each)
2/0
(2)
2/0
(1)
4+0
AC Input to Tie Cabinet Bypass (optional)
Full Load C urrent
(3) Phases, (1) Neutral---if required, (1) Ground
F
Amps 1776/1680 768
AC Output to Critical Load
Full L oad Current
(3) Phases, (1) Neutral---if required, (1) Ground
G
Amps 1776/1680 768
System Neutral Bonding Jumper
Minimum Conductor S ize
Number(See No te 27)
---
AWG or kcmil
(each)
3/0
(2)
3/0
(1)
NOTE: Callout letters D, F,andG map to Drawing 164201604---4, sheets 4 of 6, 5 of 6,
and 6 of 6.