Powerware 100160 kVA Power Supply User Manual


 
164201604---2 1 of 2
PHYSICAL FEATURES AND REQUIREMENTS
091505A
DESCRIPTION:
DATE:
DRAWING NO: SHEET:
REVISION:
Installation Information
A-3
EATON Powerware
®
9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com
1. The UPS equipment operating environment must meet t h e weight requirements shown in
Table A and the size requirements shown on Drawing 164201604---9.
2. The UPS cabinet is palleted separately for shipping.
3. Donottiltcabinetsmorethan10˚ during handling.
4. Dimensions are in millimeters (inches).
5. Thecabinetcanbeinstalledinline-up-and-match or standalone configurations.
Table A. UPS Cabinet Weight
Model
Voltage
Weight
kg (lb)
Input Output Shipping Installed Point Loading
Powerware 9390---120/100
208V/220V 208V/220V 531 (1170) 504 (1110) 6 at 84 (185)
480V 480V 467 (1030) 440 (970) 6 at 73 (162)
Powerware 9390---120/120
208V/220V 208V/220V 531 (1170) 553 (1110) 6 at 84 (185)
480V 480V 467 (1030) 440 (970) 6 at 73 (162)
Powerware 9390---160/100
208V/220V 208V/220V
581 (1280) 553 (1220) 6 at 92 (204)
480V 480V
Powerware 9390---160/120
208V/220V 208V/220V
581 (1280) 553 (1220) 6 at 92 (204)
480V 480V
Powerware 9390---160/160
208V/220V 208V/220V
581 (1280) 553 (1220) 6 at 92 (204)
480V 480V
6. The clearances required around the UPS cabinet are shown in Table B.
Table B. UPS Cabinet Clearances
From Top of Cabinet Minimum clearance over the UPS cabinet i s
457.2 mm (18 in.) for ventilation
From Front of Cabinet 914.4 mm (36 inches) working space
From Back of Cabinet None required
From Right Side of Cabinet None required
From Left Side of Cabinet None required