Powerware 100160 kVA Power Supply User Manual


 
E1, E2, E3
BATTERY
BREAKER
UPS SYSTEM ONELINE DRAWING
032406D
164201604---4
DESCRIPTION:
DATE:
DRAWING NO: SHEET:
REVISION:
UPS CABINET
INVERTER
RECTIFIER
STATIC
SWITCH
REMOTE EPO
BUILDINGALARMS
AC OUTPUT
TO
CRITICAL LOAD
AC INPUT TO
UPS RECTIFIER
3 WIRE A ---B ---C
AC INPUT
TO BYPASS
3 or 4 WIRE A ---B ---C
ROTATION
ROTATION
(See Drawing 164201604---8)
POWERWARE 9390 120/100, 120/120, 160/100 160/120
AND 160/160 208/220V INPUT AND OUTPUT AND
160/100, 160/120 AND 160/160 480V INPUT AND OUTPUT
UPS SYSTEM
SINGLE-FEED OR DUAL-FEED
INPUT
CONTACTOR
(K1)
BATTERY
CONVERTER
BATTERY
CABINET
X-SLOT
INTERFACE
(Optional)
(DUAL FEED)
AC INPUT TO
UPS RECTIFIER AND BYPASS
(DUAL FEED)
(SINGLE-FEED)
FUSE
BACKFEED
CONTACTOR
(K5)
OUTPUT
CONTACTOR
(K3)
E4. E5
E9, E10,
E11, E12
FUSE
3 or 4 WIRE A ---B ---C
ROTATION
ALARMRELAY
FUSE
INTERFACE
BOARD
BATTERY AUX
BATTERY UVR
A
B
C
D
E6, E7, E8, E12
NOTE: 1. A minimum of two separate feeds with
upstream feeder breakers, or one feed
with two upstream feeder breakers, must
be provided: one for the UPS and one
for the IAC bypass input. DO NOT use
one feed or a single-feeder breaker to
supply both the UPS and the IAC
.
2. Move bypass contactor wires to
bypass terminals for dual-feed.
3. If the load requires a neutral, a bypass
neutral feeder must be supplied.
2of6
SERIAL NUMBER SEVENTH
DIGITAT“A
Installation Information
A-7
EATON Powerware
®
9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com