Powerware 100160 kVA Power Supply User Manual


 
POWER WIRING INSTALLATION NOTES
A
164201604---5
091505
7of15
DESCRIPTION:
DATE:
DRAWING NO: SHEET:
REVISION:
Installation Information
A-18
EATON Powerware
®
9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com
Table J. Power Cable Conduit Requirements (Cont’d)
UPS Model Voltage Terminal
Number of
Wires in
Conduit
Minimum Conduit
TradeSize(inches)
Number of
Conduits
Powerware
9390---160/160
208/220
AC
AC Input to UPS
(A,B,C,Gnd)
4 3-1/2 2
AC Input to Bypass
(A,B,C,Neut,Gnd)
5 3-1/2 2
Output
(A,B,C,Neut,Gnd)
5 3-1/2 2
DC
Battery
(Positive), (Negative), Gnd
5 2-1/2 1
Powerware
9390---160/160
480
AC
AC Input to UPS
(A,B,C,Gnd)
4 2 2
AC Input to Bypass
(A,B,C,Neut,Gnd)
5 2 2
Output
(A,B,C,Neut,Gnd)
5 2 2
DC
Battery
(Positive), (Negative), Gnd
5 2-1/2 1