Powerware 100160 kVA Power Supply User Manual


 
Installing the UPS System
3-13
EATON Powerware
®
9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com
12. Remove the screws securing the bottom and right side internal safety shield panels
and remove the panels to gain access to the bottom conduit landing plate.
NOTE
When installing UV trip and Aux battery interface wiring to the UPS interface
terminals, conduit must be installed between the UPS and battery cabinets.
13. Remove the UPS cabinet top or bottom conduit landing plate to drill or punch
conduit holes (see Drawing 164201604-6 on page A-27).
14. Reinstall the conduit landing plate and install the conduit.
15. Route the UV trip and Aux wiring from the battery cabinet to the UPS.
16. Connect the wiring to the TB2 terminals.
17. If wiring X-Slot connections, proceed to paragraph 3.2.7.3; otherwise, proceed to
Step 18.
18. When all wiring is complete, reinstall the safety shield panels removed in previous
steps. Secure with the retained hardware.
19. Close the control panel door and secure with the retained hardware.
20. Reinstall the doors removed previously and secure with the retained hardware.
21. Close the doors and secure the latch.
3.2.7.3 X-Slot Connections
NOTE LAN and telephone drops for use with X-Slot connectivity cards must be provided
by facility planners or the customer.
NOTE When installing external wiring to X-Slot cards, conduit must be installed to the
UPS cabinet. When installing internal wiring to X-Slot terminals, route the wiring
through the internal opening in the X -Slot communication bay.
For installation and setup of an X-Slot card, please contact Powerware (see page 1-6).
To install wiring to connections:
1. If not already installed, install the LAN and telephone drops.
2. Unfasten the front door latch and swing the door open.
3. Remove the UPS cabinet X-Slot conduit landing plate to drill or punch conduit
holes (see Drawing 164201604-6 on page A-27).
4. Reinstall the conduit landing plate and install the conduit.
5. Route and install the LAN, telephone, and other cables to the appropriate X-Slot
cards.