Powerware 100160 kVA Power Supply User Manual


 
Using t he Control Panel
9-19
EATON Powerware
®
9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com
9.2.6 Maximum Current Log
Press the METERS pushbutton on the main menu bar to display the Unit Meter screens.
Scroll through the meter screens using the
or pushbuttons on the menu bar until the
Maximum Current Log Summary screen is displayed.
NOTE
The Maximum Current Log is available only when the mini-CSB is installed.
The maximum current log collects information on events where the unit load exceeds a
user-defined current limit within a user-defined time interval. The user can c hoose a time
period up to 9999 minutes and a load limit up to 100%. The user can also select whether
thelimitdefinedisathree-phaseaverageoftheindividualphasecurrentsorisalimit
defined for each phase individually. In the first case an event is logged if the average across
the phases exceeds the defined limit within a given time period and in the second case an
event is logged if any individual phase exceeds the defined limit within a given time period.
The Maximum Current Log Summary screen displays the number of times the limit has
been exceeded, the date of the last log reset, the maximum percent of full load, and the
total time over the limit. It also displays the average percent load over the limit. This
measurement differs, depending on whether a three-phase average or an individual phase
measurement is selected. Figure 9-21 shows the Maximum Current Log Summary screen.
MAXIMUM CURRENT LOG SUMMARY
LOG
LAST LOG RESET
AVERAGE % OF FULL LOAD
TOTAL TIME OVER LIMIT
MAXIMUM % OF FULL LOAD
5
08/04/2005
** MINUTES
NUMBER OF TIMES OVER LIMIT
*** . ** %
*** . ** %
SETUP
Figure 9-21. Maximum Current Log Summary Screen