Powerware 100160 kVA Power Supply User Manual


 
POWER WIRING INSTALLATION NOTES
032406B
164201604---5
12 of 15
DESCRIPTION:
DATE:
DRAWING NO: SHEET:
REVISION:
Installation Information
A-23
EATON Powerware
®
9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com
Table O. INPUT/OUTPUT Ratings for Powerware 9390---120/100 an d 9390---160/100 Parallel Systems
Configuration Units Rating 50/60 Hz
BasicUnitRatingat0.9laggingpFload
kVA
kW
100
90
100
90
Input and Bypass Input
Output
VOLTS
VOLTS
208/220
208/220
480
480
All
AC Input from UPM
Full L oad Current for each Module
(3) Phases, (1) Neutral---if required, (1) Ground
D
Amps 278/262 120
Minimum Conductor Size for each Module
NumberperPhaseforeachModule
AWG or kcmil
(each)
See Table E through
TableGforwiresize.
1+1
AC Input to Tie Cabinet Bypass (optional)
Full Load C urrent
(3) Phases, (1) Neutral---if required, (1) Ground
F
Amps 278/262 120
AC Output to Critical Load
Full L oad Current
(3) Phases, (1) Neutral---if required, (1) Ground
G
Amps 278/262 120
System Neutral Bonding Jumper
Minimum Conductor S ize
Number(See No te 27)
---
AWG or kcmil
(each)
1/0
(1)
4
(1)
2+0
and
2+1
AC Input to Tie Cabinet Bypass (optional)
Full Load C urrent
(3) Phases, (1) Neutral---if required, (1) Ground
F
Amps 556/524 240
AC Output to Critical Load
Full L oad Current
(3) Phases, (1) Neutral---if required, (1) Ground
G
Amps 556/524 240
System Neutral Bonding Jumper
Minimum Conductor S ize
Number(See No te 27)
---
AWG or kcmil
(each)
3/0
(1)
1/0
(1)
3+0
and
3+1
AC Input to Tie Cabinet Bypass (optional)
Full Load C urrent
(3) Phases, (1) Neutral---if required, (1) Ground
F
Amps 834/786 360
AC Output to Critical Load
Full L oad Current
(3) Phases, (1) Neutral---if required, (1) Ground
G
Amps 834/786 360
System Neutral Bonding Jumper
Minimum Conductor S ize
Number(See No te 27)
---
AWG or kcmil
(each)
1/0
(2)
2/0
(1)
4+0
AC Input to Tie Cabinet Bypass (optional)
Full Load C urrent
(3) Phases, (1) Neutral---if required, (1) Ground
F
Amps 1112/1048 480
AC Output to Critical Load
Full L oad Current
(3) Phases, (1) Neutral---if required, (1) Ground
G
Amps 1112/1048 480
System Neutral Bonding Jumper
Minimum Conductor S ize
Number(See No te 27)
---
AWG or kcmil
(each)
2/0
(2)
2/0
(1)
NOTE: Callout letters D, F,andG map to Drawing 164201604---4, sheets 4 of 6, 5 of 6,
and 6 of 6.