Powerware 100160 kVA Power Supply User Manual


 
POWER WIRING INSTALLATION NOTES
091505A
164201604---5
11 of 15
DESCRIPTION:
DATE:
DRAWING NO: SHEET:
REVISION:
Installation Information
A-22
EATON Powerware
®
9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com
28. See Drawing 164201604---7 for UPM terminal locations and Table H or Table I for
termination requirements.
29. Setup of the CAN Bridge card for parallel operation must be performed by an authorized
Eaton Customer Service Engineer
. Contact service to schedule a date.
30. For parallel system circuit breaker ratings, see appropriate information in Table N .
31. For parallel system ratings, see the appropriate information in Ta ble O through Table Q.
Table N. Recommended UPM Output (MOB), Main Output (MIS), and Bypass (MBP)
Circuit Breaker Ratings
UPM Model Configuration
Output Voltage
208V/220V 480V
MOB MIS MBP MOB MIS MBP
9390---120/100
9390---160/100
1+1 500 500 500 200 200 200
2+0 and 2+1 500 1000 1000 200 400 400
3+0 and 3+1 500 1600 1600 200 600 600
4+0 500 2000 2000 200 800 800
9390---120/120
9390---160/120
1+1 500 500 500 200 200 200
2+0 and 2+1 500 1000 1000 200 400 400
3+0 and 3+1 500 1600 1600 200 600 600
4+0 500 2000 2000 200 800 800
9390---160/160
1+1 600 600 600 250 250 250
2+0 and 2+1 600 1200 1200 250 500 500
3+0 and 3+1 600 2000 2000 250 800 800
4+0 600 2400 2400 250 1000 1000