Rack-mounting the EPS-LD Power Supply
NOTE
When installing an EPS-LD in a rack, make sure air vents are not restricted. Allow for elevated ambient operating
temperatures when the EPS-LD is installed adjacent to other equipment. Be sure you mount the equipment in the
rack so that the load is evenly distributed.
To rack-mount each EPS-LD unit:
1 Place the EPS-LD unit upright on a stable surface, with the side you want to face to the front of the
switch toward you.
2 Remove the mounting bracket kit from the packaging.
3 Attach the mounting brackets as follows:
a Place a mounting bracket over the mounting holes on one side of the unit (see Figure 150).
b Insert the provided screws and fully tighten them using a screwdriver.
Figure 150: Attaching the Mounting Bracket
c Repeat steps a and b for the other side of the EPS-LD unit.
4 Slide the EPS-LD into a 19-inch rack and secure it using appropriate rack-mount screws.
NOTE
Extreme Networks recommends that you position the EPS-LD so that the output connectors are on the same side
as the external connector on the connecting switch. If you mount the EPS-LD with the connectors facing in the
opposite direction from the Summit switch connector, leave at least 1 U between the switch and the EPS-LD
through which to slide the power cords. Do not route the power cords around the equipment rack.