This equipment can be connected between buildings if any one of the following conditions is true:
Cable runs between buildings are less then 140 feet long.
Cable runs between buildings are directly buried.
Cable runs between buildings are in an underground conduit, where a continuous metallic cable
shield or a continuous metallic conduit containing the cable is bonded to each building grounding
electrode system.
CAUTION
Failure follow these requirements for cable routing conditions may expose the user to electrical shock and expose
the unit to errors or damage.
WARNING!
The intra-building ports of the equipment or subassembly are suitable for connection to intrabuilding or unexposed
wiring or cabling only. The intra-building port(s) of the equipment or subassembly MUST NOT be metallically
connected to interfaces that connect to the outside plant (OSP) or its wiring. These interfaces are designed for use
as intra-building interfaces only (Type 2 or Type 4 ports as described in GR-1089-CORE, Issue 4) and require
isolation from the exposed OSP cabling. The addition of Primary Protectors is not sufficient protection in order to
connect these interfaces metallically to OSP wiring.
PoE Devices
When connecting power over Ethernet (PoE) devices to a PoE switch, all connections between the PoE
device and the switch must remain inside the same building and use a low-voltage power distribution
system per IEEE 802.3af.
Selecting Power Supply Cords
Extreme Networks does not include power input cords in the product box. To purchase a power cord
for your product and for your specific country, contact your local Extreme Networks Channel Account
Manager or Sales Manager, or purchase a cord from your local supplier.
To locate a Sales Manager or Partner in your region visit:
http://www.extremenetworks.com/how-to-buy/how-to-buy.aspx
The following are requirements for power cords used on AC-powered Summit family switches and
compatible external power supplies:
The power cord must be agency-certified for the country of use.
The power cord must have an IEC320-C13 connector for connection to the switch or external power
supply.
The power cord must have an appropriately rated and approved wall plug applicable to the country
of installation.
For cords up to 6 feet (2 m) long, the wire size must be 18 AWG (.75 mm
2
) minimum; over 6 feet, the
minimum wire size is 16 AWG (1.0 mm
2
).