INSTALLATION PROCEDURE
Figure 008-8 Stripped Length of Main and Branch Cable
NAP-200-008
Sheet 11/13
Connection of Power and Ground
Cables from the Power Equipment
Table 008-1 Stripped Length
APPLICABLE TERMINAL
STRIPPED MAIN-WIRE LENGTH I
1
[inch (mm)]
STRIPPED MAIN-WIRE LENGTH I
2
[inch (mm)]
T-20 Approx. 1.2 (28) Approx. 1.0 (24)
T-26 1.3 (32) 1.2 (28)
T-44 1.5 (37) 1.3 (33)
T-60 1.6 (40) 1.5 (36)
T-76 1.7 (42) 1.6 (39)
T-98 1.8 (44) 1.7 (41)
T-122 1.7–1.9 (43–46) 1.6–1.7 (40–43)
T-154 2.0 (49) 1.9 (46)
T-190 2.3 (57) 2.2 (54)
T-240 2.5 (63) 2.4 (60)
T-288 2.8 (69) 2.6 (66)
T-365 3.0 (75) 2.9 (72)
T-98
Sum of the cross sections of the main and branching, or the main and extension cables.
Type of clamp terminal (T type)
I
1
MAIN CABLE
CONDUCTOR
BRANCH CABLE
I
2
T TYPE
CLAMP-
TERMINAL