The miscellaneous settings include scaling factors, initialization modes, and others. This
section covers some of the most important settings you may need to configure.
Function Code Display Restriction – The inverter has the (optional) capability to suppress the
display and editing of certain parameters. Use B037 to select the display options. The purpose
of this feature is to hide particular secondary parameters that become unused or not applicable
based on more fundamental parameter settings. For example, setting A001 = 01 configures the
inverter to get its frequency command from the front keypad potentiometer. In this case, the
inverter will not use the analog inputs nor their adjustment parameters for an external frequency
command.
For example, you can set B037=01 to have the inverter suppress the displaying of all analog
input parameters when A001=01, as shown in the first row of the following table.
“B” Function
Run
Mode
Edit
Lo Hi
Defaults
Units
SRW Display
Func.
Code
Name Description
–FE
(EU)
–FU
(US)
–FR
(JP)
B034 Run/power-on warning
time
Range is 0 to 65,530 hours ✘ ✔ 0. 0. 0. hrs.
>b034 TIME
WARN 00000
B035 Rotational direction
restriction
Three option codes:
00 Enable for both dir.
01 Enable for forward only
02 Enable for reverse only
✘ ✘ 00 00 00
>b035 LIMIT
F/R FREE
B036 Reduced voltage start
selection
Seven option codes:
00 Short
01, 02, 03, 04, 05 (middle)
06 Long
✘ ✔ 06 06 06
>b036 RVS
ADJUST 06
“B” Function
Run
Mode
Edit
Lo Hi
Defaults
Units
SRW Display
Func.
Code
Name Description
–FE
(EU)
–FU
(US)
–FR
(JP)
B037 Function code display
restriction
Three option codes:
00 Display all
01 Display only utilized
functions (see table
below)
02 Display user-selected
functions only (con-
figure with U01 to U12)
✘ ✔ 00 00 00
>b037 DISP
Mode ALL
Function
Code
Data
Resulting Non-displayed
Functions (when B37 = 01)
Notes
A001 01 A005, A006, A011 – A016,
A101 – A114, C081 – C083,
C121 – C123
[O], [OI], [O2] terminal
functions
A002 01, 03, 04,
05
B087 Stop key function
A019 00 A028 – A035 Multi-speed function
C001 – C008 02, 03, 04,
05