Hitachi SJ300 Series Power Supply User Manual


 
Monitoring Trip Events, History, & Conditions
Troubleshooting
and Maintenance
6–8
Trip History and
Inverter Status
We recommend that you first find the cause of the fault before attempting clearing it. When a
fault occurs, the inverter stores important performance data at the moment of the fault. To
access the data, use the monitor functions (Dxxx) and select D081 for details about the present
fault (E
n
). The previous five faults are stored in D081 to D086, with D (E
n-1
to E
n-5
). Each error
shifts D081–D085 to D082–D086, and writes the new error to D081.
The following Monitor Menu map shows how to access the error codes. When fault(s) exist,
you can review their details by first selecting the proper function: D081 is most recent, and
D086 is the oldest.
1
Error Code
Error
exists?
Output frequency at
trip point
Motor current at
trip point
DC bus voltage at
trip point
No error
Ye s
No
2
1
2
2
E07.2
60.00
4.0 0
270.0
15
18
d
081
d
086
d
082
1
1
1
1
1
Cumulative inverter
operation time
at trip point
Cumulative power-
ON time at trip point
1
2
Current Trip
Conditions
Trip History
Monitor Menu
FUNC.
FUNC.
FUNC.