SJ300 Inverter
Appendix C
C–7
Fine Tuning
Functions
“B” Group Parameters Default Setting
User
Setting
Func.
Code
Name
-FE (Europe) -FU (U.S.) -FR (Japan)
B001 Selection of restart mode 00 00 00
B002 Allowable under-voltage power
failure time
1.0 1.0 1.0
B003 Retry wait time before motor restart 1.0 1.0 1.0
B004 Instantaneous power failure / under-
voltage trip alarm enable
00 00 00
B005 Number of restarts on power failure /
under-voltage trip events
00 00 00
B006 Phase loss detection enable 00 00 00
B007 Restart frequency threshold 0.00 0.00 0.00
B012 Electronic thermal setting (calcu-
lated within the inverter from current
output)
Rated current
for each
inverter
Rated current
for each
inverter
Rated current
for each
inverter
B212 Electronic thermal setting (calcu-
lated within the inverter from current
output), 2nd motor
Rated current
for each
inverter
Rated current
for each
inverter
Rated current
for each
inverter
B312 Electronic thermal setting (calcu-
lated within the inverter from current
output), 3rd motor
Rated current
for each
inverter
Rated current
for each
inverter
Rated current
for each
inverter
B013 Electronic thermal characteristic 01 01 00
B213 Electronic thermal characteristic,
2nd motor
01 01 00
B313 Electronic thermal characteristic,
3rd motor
01 01 00
B015 Free setting, electronic thermal
frequency (1)
0. 0. 0.
B016 Free setting, electronic thermal
current (1)
0.0 0.0 0.0
B017 Free setting, electronic thermal
frequency (2)
0. 0. 0.
B018 Free setting, electronic thermal
current (2)
0.0 0.0 0.0
B019 Free setting, electronic thermal
frequency (3)
0. 0. 0.
B020 Free setting, electronic thermal
current (3)
0.0 0.0 0.0
B021 Overload restriction operation mode 01 01 01
B022 Overload restriction setting
Rated current x
1.50
Rated current x
1.50
Rated current x
1.50