“A” Group: Standard Functions
Configuring Drive
Parameters
3–10
NOTE: The base frequency must be less than or equal to the maximum frequency (ensure that
A003 ≤ A004).
A203 Base frequency setting,
2nd motor
Settable from 30 Hz to the
maximum frequency
✘ ✘ 50. 60. 60. Hz
>A203 2F-BASE
F 0060Hz
A303 Base frequency setting,
3rd motor
Settable from 30 Hz to the
maximum frequency
✘ ✘ 50. 60. 60. Hz
>A303 3F-BASE
F 0060Hz
A004 Maximum frequency
setting
Settable from 30 Hz to
400 Hz
✘ ✘ 50. 60. 60. Hz
>A004 F-max
F 0060Hz
A204 Maximum frequency
setting, 2nd motor
Settable from 30 Hz to
400 Hz
✘ ✘ 50. 60. 60. Hz
>A204 2F-max
F 0060Hz
A304 Maximum frequency
setting, 3rd motor
Settable from 30 Hz to
400 Hz
✘ ✘ 50. 60. 60. Hz
>A304 3F-max
F 0060Hz
“A” Function
Run
Mode
Edit
Lo Hi
Defaults
Units
SRW Display
Func.
Code
Name Description
–FE
(EU)
–FU
(US)
–FR
(JP)