Hitachi SJ300 Series Power Supply User Manual


 
Hitachi EMC Recommendations
Appendix D
D–4
Hitachi EMC Recommendations
WARNING: This equipment should be installed, adjusted, and serviced by qualified personal
familiar with construction and operation of the equipment and the hazards involved. Failure to
observe this precaution could result in bodily injury.
Use the following checklist to ensure the inverter is within proper operating ranges and
conditions.
1. The power supply to SJ300 inverters must meet these specifications:
Voltage fluctuation+/- 10% or less
Voltage imbalance +/- 3% or less
Frequency variation +/- 4% or less
Voltage distortion THD = 10% or less
2. Installation measure:
Use a filter designed for SJ300 inverter.
3. Wiring:
Shielded wire (screened cable) is required for motor wiring, and the length must be less
than 50 meters.
The carrier frequency setting must be less than 5 kHz to satisfy EMC requirements.
Separate the power input and motor wiring from the signal/process circuit wiring.
4. Environmental conditions—when using a filter, follow these guidelines:
Ambient temperature: –10 to 40 °C
Humidity: 20 to 90% RH (non-condensing)
Vibration: 5.9 m/sec
2
(0.6 G) 10 ~ 55Hz, SJ300–004xxx to SJ300–220xxx
2.94 m/sec
2
(0.3 G) 10 ~ 55Hz, SJ300–300xxx to SJ300–1500xxx
Location: 1000 meters or less altitude, indoors (no corrosive gas or dust)