Xantrex Technology SW Plus 4024 Power Supply User Manual


 
AC Wiring
976-0043-01-02 3–37
b) from the neutral in the generator disconnect to the inverter
NEUTRAL 2 terminal.
3. Connect HOT (black) wires:
a) from the generator GEN HOT OUT terminal to the circuit
breaker in the generator disconnect, and
b) from the circuit breaker in the generator disconnect to the inverter
AC2 GEN terminal.
4. Torque all inverter terminal block connections to 25 inch-pounds.