Xantrex Technology SW Plus 4024 Power Supply User Manual


 
Configuration Settings
B–10 976-0043-01-02
Advanced Setup Menu
Table B-5 provides a list of Advanced Setup Menu headings and menu
items, with available set points. This table also provides the default
settings for each menu item as programmed in the factory. The last
column “User Settings” is provided for you to write in the settings
specific to your installation.
Table B-5
Advanced Setup Default and User Settings for the Sine Wave Plus 2524 and
2548 Models
Advanced Setup Menus
Sine Wave Plus 2524 Sine Wave Plus 2548
User
Settings
Range/
Display
Default
Settings
Range/
Display
Default
Settings
20 Silent Setup Menu See “20 Silent Setup Menu” on page 7–13 for details.
20A Refloat High Volts DC 16.1 to 33.9 28.4 32.2 to 67.8 56.8
20B Refloat Low Volts DC 16.1 to 33.8 25.0 32.2 to 67.8 50.0
20C Float Done Amps AC 00 to 40 10 00 to 40 10
20D Must Float Time Min 00 to 255 05 00 to 255 05
21 Grid AC1 Usage Menu See “21 Grid (AC1) Usage Menu” on page 7–16 for details.
21A Grid Usage SB BX SB BX SB SB BX SB
21B Grid Usage Begin h:m 00:00 to
23:50
21:00 00:00 to
23:50
21:00
21C Grid Usage End h:m 00:00 to
23:50
21:00 00:00 to
23:50
21:00
22 Battery Xfer (BX) Menu See “22 Battery Xfer (BX) Menu” on page 7–18 for details.
22A High Xfer (HBX) Vdc 16.1 to 33.9 27.0 32.2 to 67.8 54.0
22B Low Xfer (LBX) Vdc 16.1 to 33.8 23.0 32.2 to 67.8 46.0
23 ALM Relays Menu See “23 ALM Relays Menu” on page 7–19 for details.
23A RY9 Vdc Energized 22.1 to 35.5 26.0 44.2 to 71.0 52.0
23B RY9 Vdc DeEnergized 20.0 to 35.5 22.0 40.0 to 71.0 44.0
23C RY9 Delay at DeEngz. Min 00 to 255 10 00 to 255 10
23D RY10 VDC Energized 10.0 to 32.0 28.8 20.0 to 64.0 57.6
23E RY10 VDC DeEnergized 10.0 to 32.0 26.8 20.0 to 64.0 53.6
23F RY10 Delay at DeEngz. Min 00 to 255 10 00 to 255 10
23G RY11 Mode Cooldown
Error
Error Cooldown
Error
Error