Xantrex Technology SW Plus 4024 Power Supply User Manual


 
Advanced Setup
7–6 976-0043-01-02
24B Gen Run Time Stop h:m 00:00 to 23:50 08:00 00:00 to 23:50 08:00 page 7–27
24C Quiet Time Begin h:m 00:00 to 23:50 08:00 00:00 to 23:50 08:00 page 7–27
24D Quiet Time End h:m 00:00 to 23:50 08:00 00:00 to 23:50 08:00 page 7–28
24E Gen Exercise Period
Days
00 to 255 30 00 to 255 30 page 7–28
24F Gen Exercise Timer Min 00 to 255 15 00 to 255 15 page 7–28
24G Gen Cooldown Timer
Min
00 to 255 02 00 to 255 02 page 7–28
24H RN2/Max Gen Run h:m 00:00 to 23:50 08:00 00:00 to 23:50 08:00 page 7–29
End Menu 24
25 Gen Starting Details Menu See “25 Gen Starting Details Menu” on page 7–29 for details.
25A RY7 Mode GS RN1 RN2 GS GS RN1 RN2 GS page 7–30
25B Gen Warm-up
Second/Minute
0 to 127
/0 to 127
10
Seconds
0 to 127
/0 to 127
10 Seconds page 7–37
25C Pre Crank Seconds 00 to 255 10 0 to 255 10 page 7–37
25D Max Cranking Seconds 01 to 15 10 01 to 15 10 page 7–37
25E Post Crank Seconds 00 to 255 30 00 to 255 30
End Menu 25
26 Gen Auto Run Setup Menu See “26 Gen Auto Run Setup Menu” on page 7–38 for details.
26A Load Start Amps AC 00 to 63 33 00 to 63 33 page 7–38
26B Load Start Delay Min 00.0 to 25.5 05.0 00.0 to 25.5 05.0 page 7–38
26C Load Stop Delay Min 00.0 to 25.5 05.0 00.0 to 25.5 05.0 page 7–38
26D 24 hr Start Volts DC 10.0 to 35.5 24.6 20.0 to 71.0 49.2 page 7–38
26E 2 hr Start Volts DC 10.0 to 35.5 23.6 20.0 to 71.0 47.2 page 7–38
26F 15 min Start Volts DC 10.0 to 35.5 22.6 20.0 to 71.0 45.2 page 7–39
26G Read LBCO 30 sec Start LBCO setting
(11C)
22.0
Read Only
LBCO setting
(11C)
44.0
Read Only
page 7–39
End Menu 26
27 Save/Restore Settings Menu See “27 Save/Restore Settings Menu” on page 7–39 for details.
Table 7-2
Advanced Setup Default Settings for the Sine Wave Plus 4024 and 4048 Models
Advanced Setup Menus
Sine Wave Plus 4024 Sine Wave Plus 4048
See PageRange/Display
Default
Settings Range/Display
Default
Settings