Xantrex Technology SW Plus 4024 Power Supply User Manual


 
Menu Item Descriptions
976-0043-01-02 6–21
The following settings (Table 6-5) are guidelines only. Refer to your
battery vendor for specific settings and battery maintenance guidelines.
Table 6-4
Battery Voltages For Setting Charging Parameters
Battery Type
BULK VOLTS FLOAT VOLTS
Equalization Charge
Process
Set
Temp
Comp
24-volt
models
48-volt
models
24-volt
models
48-volt
models
Sealed Gel
Lead Acid
28.2 Vdc 56.4 Vdc 27.2 Vdc 54.4 Vdc Not recommended -
consult manufacturer
LeadAcid
AGM
Lead Acid
28.8 Vdc 57.6 Vdc 26.8 Vdc 53.6 Vdc Charge to 31.0 Vdc
(24-volt models) or 62
Vdc (48-volt models) or
as per manufacturer
recommendations
LeadAcid
Maintenance-Free
RV/Marine
Lead Calcium
Battery
28.8 Vdc 57.6 Vdc 26.8 Vdc 53.6 Vdc Not recommended -
consult manufacturer
LeadAcid
Deep-cycle,
Liquid Electrolyte
Lead Antimony
Battery
29.2 Vdc 58.4 Vdc 26.8 Vdc 53.6 Vdc Charge to 31.0 Vdc
(24-volt models) or 62
Vdc (48-volt models) or
as per manufacturer
recommendations
LeadAcid
NiCad or NiFe
Alkaline Battery
(using 10 cells in
series)
32.0 Vdc 64.0 Vdc 29.0 Vdc 58.0 Vdc Consult Manufacturer NiCad
Table 6-5
Battery Charging Current and Timer Default Settings
Menu Item
SW Plus
2524
Default
Settings
SW Plus
2548
Default
Setting
SW Plus
4024
Default
Settings
SW Plus
4048
Default
Setting
SW Plus
5548
Default
Setting
12E Max Charge Amps 20 amps 20 amps 30 amps 30 amps 40 amps
12F Bulk Done Amps AC 10 amps 10 amps 10 amps 10 amps 10 amps
12G EQ Vdc Done Timer h:m 02:00 02:00 02:00 02:00 02:00
12H Max Bulk/EQ Timer h:m 05:00 05:00 05:00 05:00 05:00
12I Temp Comp LeadAcid LeadAcid LeadAcid LeadAcid LeadAcid