Xantrex Technology SW Plus 4024 Power Supply User Manual


 
Advanced Setup Summary
976-0043-01-02 7–3
21C Grid Usage End h:m 00:00 to 23:50 21:00 00:00 to 23:50 21:00 page 7–18
End Menu 21
22 Battery Xfer (BX) Menu See “22 Battery Xfer (BX) Menu” on page 7–18 for details.
22A High Xfer (HBX) Vdc 16.1 to 33.9 27.0 32.2 to 67.8 54.0 page 7–19
22B Low Xfer (LBX) Vdc 16.1 to 33.8 23.0 32.2 to 67.8 46.0 page 7–19
End Menu 22
23 ALM Relays Menu See “23 ALM Relays Menu” on page 7–19 for details.
23A RY9 VDC Energized 22.1 to 35.5 26.0 44.2 to 71.0 52.0 page 7–20
23B RY9 VDC DeEnergized 20.0 to 35.5 22.0 40.0 to 71.0 44.0 page 7–20
23C RY9 Delay at DeEngz.
Min
00 to 255 10 00 to 255 10 page 7–20
23D RY10 VDC Energized 10.0 to 32.0 28.8 20.0 to 64.0 57.6 Vdc page 7–20
23E RY10 VDC DeEnergized 10.0 to 32.0 26.8 20.0 to 64.0 53.6 Vdc page 7–21
23F RY10 Delay at DeEngz.
Min
00 to 255 10 00 to 255 10 page 7–21
23G RY11 Mode Cooldown Error Error Cooldown Error Error page 7–21
End Menu 23
24 Generator Timers Menu See “24 Generator Timers Menu” on page 7–26 for details.
24A Gen Run Time Start h:m 00:00 to 23:50 08:00 00:00 to 23:50 08:00 page 7–27
24B Gen Run Time Stop h:m 00:00 to 23:50 08:00 00:00 to 23:50 08:00 page 7–27
24C Quiet Time Begin h:m 00:00 to 23:50 08:00 00:00 to 23:50 08:00 page 7–27
24D Quiet Time End h:m 00:00 to 23:50 08:00 00:00 to 23:50 08:00 page 7–28
24E Gen Exercise Period Days 00 to 255 30 00 to 255 30 page 7–28
24F Gen Exercise Timer Min 00 to 255 15 00 to 255 15 page 7–28
24G Gen Cooldown Timer
Min
00 to 255 02 00 to 255 02 page 7–28
24H RN2/Max Gen Run h:m 00:00 to 23:50 08:00 00:00 to 23:50 08:00 page 7–29
End Menu 24
25 Gen Starting Details Menu See “25 Gen Starting Details Menu” on page 7–29 for details.
Table 7-1
Advanced Setup Default Settings for the Sine Wave Plus 2524 and 2548 Models
Advanced Setup Menus
Sine Wave Plus 2524 Sine Wave Plus 2548
See PageRange/Display
Default
Settings Range/Display
Default
Settings