Xantrex Technology SW Plus 4024 Power Supply User Manual


 
Basic Setup Programming
6–6 976-0043-01-02
Table 6-3
Basic Setup Menu Default Settings for the Sine Wave Plus 5548 Model
Basic Setup Menus
Sine Wave Plus 5548
See Page
Range/
Display Default
10 Time of Day Setup Menu See “10 Time of Day Setup Menu” on page 6–11 for details.
10A Set Hour 00:00:00 to
23:50:00
00:00:00 page 6–11
10B Set Minute 00:00:00 to
00:09:00
00:00:00 page 6–11
10C Set Second 00 to 59 00:00:00 page 6–12
End Menu 10
11 Inverter Setup Menu See “11 Inverter Setup Menu” on page 6–12 for details.
11A High Battery Cut Out Vdc 32.2 to 68.0 64.0 page 6–12
11B Low Battery Cut In Vdc 32.2 to 67.8 52.0 page 6–12
11C Low Battery Cut Out Vdc 32.0 to 67.8 44.0 page 6–13
11D LBCO Delay Minutes 01 to 255 15 page 6–13
11E Search Watts (SRCH) 00 to 248 08 page 6–14
End Menu 11
12 Battery Charging Menu See “12 Battery Charging Menu” on page 6–19 for details.
12A Finish Stage SILENT
FLOAT
FLOAT page 6–19
12B Bulk Volts DC 40.0 to 64.0 57.6 page 6–20
12C Float Volts DC 40.0 to 64.0 53.6 page 6–20
12D Equalize Volts DC 40.0 to 64.0 57.6 page 6–20
12E Max Charge Amps AC 01 to 45 40 page 6–22
12F Bulk Done Amps AC 00 to 50 10 page 6–23
12G EQ Vdc Done Timer 00:00 to
23:50
02:00 page 6–24
12H Max Bulk/EQ Timer 00:00 to
23:50
05:00 page 6–25
12I Temp Comp LeadAcid
NiCad
LeadAcid page 6–25
End Menu 12