Xantrex Technology SW Plus 4024 Power Supply User Manual


 
Basic Setup Programming
6–4 976-0043-01-02
14C Push GEN for factory
defaults
Push GEN for factory defaults page 6–30
End Menu 14
END BASIC SETUP MENU
Table 6-2
Basic Setup Menu Default Settings for the Sine Wave Plus 4024 and 4048 Models
Basic Setup Menus
Sine Wave Plus 4024 Sine Wave Plus 4048
See Page
Range/
Display Default
Range/
Display Default
10 Time of Day Setup Menu See “10 Time of Day Setup Menu” on page 6–11 for details.
10A Set Hour 00:00:00 to
23:50:00
00:00:00 00:00:00 to
23:50:00
00:00:00 page 6–11
10B Set Minute 00:00:00 to
00:09:00
00:00:00 00:00:00 to
00:09:00
00:00:00 page 6–11
10C Set Second 00 to 59 00:00:00 00 to 59 00:00:00 page 6–12
End Menu 10
11 Inverter Setup Menu See “11 Inverter Setup Menu” on page 6–12 for details.
11A High Battery Cut Out Vdc 16.1 to 34.0 32.0 32.2 to 68.0 64.0 page 6–12
11B Low Battery Cut In Vdc 16.1 to 33.9 26.0 32.2 to 67.8 52.0 page 6–12
11C Low Battery Cut Out Vdc 11.0 to 33.9 22.0 32.0 to 67.8 44.0 page 6–13
11D LBCO Delay Minutes 01 to 255 15 01 to 255 15 page 6–13
11E Search Watts (SRCH) 00 to 248 08 00 to 248 08 page 6–14
End Menu 11
12 Battery Charging Menu See “12 Battery Charging Menu” on page 6–19 for details.
12A Finish Stage SILENT
FLOAT
FLOAT SILENT
FLOAT
FLOAT page 6–19
12B Bulk Volts DC 20.0 to 32.0 28.8 40.0 to 64.0 57.6 page 6–20
12C Float Volts DC 20.0 to 32.0 26.8 40.0 to 64.0 53.6 page 6–20
12D Equalize Volts DC 20.0 to 32.0 28.8 40.0 to 64.0 57.6 page 6–20
Table 6-1
Basic Setup Menu Default Settings for the Sine Wave Plus 2524 and 2548 Models
Basic Setup Menus
Sine Wave Plus 2524 Sine Wave Plus 2548
See Page
Range/
Display Default
Range/
Display Default