Xantrex Technology SW Plus 4024 Power Supply User Manual


 
Operation
8–22 976-0043-01-02
04 Meters Menu
The Meters Menu provides information about system performance. The
menus under this heading are read-only. This information includes the
following menu items to assist the user in monitoring system
performance:
04A Battery Actual Volts DC
04B Battery Compensated Volts DC
04C Inverter/Charger Amps AC
04D Input Amps AC
04E Load Amps AC
04F Inverter Volts AC
04G Grid (AC1) Volts AC
04H Generator (AC2) Volts AC
04I Frequency Hertz
04J Maximum Bulk/EQ Time
04K Battery Temp Degrees C
04L Fan Speed
04A Battery Actual Vdc
This menu item displays the actual DC battery voltage. This value is used
for setting the following menu items.
11C Low Battery Cut Out Vdc
11A High Battery Cut Out Vdc
22B Low Battery Xfer Vdc
11B Low Battery Cut In Vdc
22A High Battery Xfer Vdc
Note: The AC ammeters have an approximate 1-amp tolerance. Additionally,
the meters provided in menus 04C, 04D and 04E measure the real, in-phase AC
component of the current. This is the portion of the power that is actually drawn
from the batteries, allowing better estimation of the DC power consumed by the
load or the battery charger. Measurements taken with conventional AC DVMs
usually read apparent current and may differ from these readings.