Advanced Setup Menu
976-0043-01-02 B–11
24 Generator Timers Menu See “24 Generator Timers Menu” on page 7–26 for details.
24A Gen Run Time Start h:m 00:00 to
23:50
08:00 00:00 to
23:50
08:00
24B Gen Run Time Stop h:m 00:00 to
23:50
08:00 00:00 to
23:50
08:00
24C Quiet Time Begin h:m 00:00 to
23:50
08:00 00:00 to
23:50
08:00
24D Quiet Time End h:m 00:00 to
23:50
08:00 00:00 to
23:50
08:00
24E Gen Exercise Period Days 00 to 255 30 00 to 255 30
24F Gen Exercise Timer Min 00 to 255 15 00 to 255 15
24G Gen Cooldown Timer Min 00 to 255 02 00 to 255 02
24H RN2/Gen Run h:m 00:00 to
23:50
08:00 00:00 to
23:50
08:00
25 Gen Starting Details Menu See “25 Gen Starting Details Menu” on page 7–29 for details.
25A RY7 Mode GS RN1 RN2 GS GS RN1 RN2 GS
25B Gen Warmup
Second/Minute
0 to 127
/0 to 127
10 Seconds 0 to 127
/0 to 127
10 Seconds
25C Pre Crank Seconds 00 to 255 10 0 to 255 10
25D Max Crank Seconds 01 to 15 10 01to15 10
25E Post Crank Seconds 00 to 255 30 00 to 255 30
26 Gen Auto Run Setup Menu See “26 Gen Auto Run Setup Menu” on page 7–38 for details.
26A Load Start Amps AC 00 to 63 20 00 to 63 20
26B Load Start Delay Min 00.0 to 25.5 05.0 00.0 to 25.5 05.0
26C Load Stop Delay Min 00.0 to 25.5 05.0 00.0 to 25.5 05.0
26D 24-hr Start Volts DC 10.0 to 35.5 24.6 20.0 to 71.0 49.2
26E 2-hr Start Volts DC 10.0 to 35.5 23.6 20.0 to 71.0 47.2
26F 15-min Start Volts DC 10.0 to 35.5 22.6 20.0 to 71.0 45.2
Table B-5
Advanced Setup Default and User Settings for the Sine Wave Plus 2524 and
2548 Models
Advanced Setup Menus
Sine Wave Plus 2524 Sine Wave Plus 2548
User
Settings
Range/
Display
Default
Settings
Range/
Display
Default
Settings