Operation
8–30 976-0043-01-02
06E EQ Charge Selected
If “Yes” is displayed, the charger is set to run in the Equalize Charge
Mode.
Be sure to monitor menu items 04I Battery Temp and 04K Read Bulk/
EQ Time when equalize charging the batteries.
6F Battery VDC < LBCO
If “Yes” is displayed, the battery voltage has dropped below the voltage
set in menu 11C Low Battery Cut Out VDC.
When the batteries have dropped below the setting for the time set in
menu 11D LBCO Delay Minutes, the inverter will shut off.
6G Battery VDC > HBCO
If “Yes” is displayed, the battery voltage has risen to or exceeded the
voltage set in menu 11A High Battery Cut Out VDC.
When the battery voltage has risen above the setting in menu 11A High
Battery Cut Out VDC and remains there for approximately one minute,
the inverter will shut off.
06H EPO Shutdown
If “Yes” is displayed, the inverter has received an Emergency Power OFF
Shutdown command from an externally located shut off switch to the
inverter’s EPO Port.
07 GSM/ALM Options Menu
The 07 GSM/ALM Options Menu displays the various conditions of the
relays on the GSM and ALM. The information provided here can assist in
finding the reason for an auto-generator start or to determine the GEN and
AUX relay state which can be used as a troubleshooting aid if necessary.
Using the GSM for auto-starting or controlling a generator is only
possible with generators that have an electric starter and are compatible
with two- or three-wire external relay control.
07A RY7 (GSM) Energized
If “Yes” is displayed, the inverter has sent out a command to energize the
relay (between the N.O. to COM connections) in the GSM.
This display can be used for troubleshooting purposes by helping to
isolate the cause of a generator problem.