Xantrex Technology SW Plus 4024 Power Supply User Manual


 
Troubleshooting
9–6 976-0043-01-02
Batteries being charged
above the Bulk/Float
setting.
If BTS is installed, it may
be in a cold area or have
fallen off the batteries.
Another DC charging
source may be on the
batteries.
Monitor the 04B Battery Temp Comp VDC while
charging.
NOTE: To bring batteries that are cold to the correct
state of charge may require charging at a higher
voltage. Remove the BTS and determine if your
voltage returns to the bulk/float voltage.
The red Error LED and
the STATUS LED
illuminate at the same
time and the inverter
shuts down.
The inverter has detected
a low battery voltage
condition. In other words,
the voltage has dropped
below the 11C Low
Battery Cut Out VDC
setting for the amount of
time set in 11D LBCO
Delay Minutes.
Restore an AC source to allow the inverter to charge
the batteries back up to acceptable levels.
To manually restart the inverter, press the red INV
button to access the 01A Inverter menu. Then select
OFF, then SRCH or ON from the display.