Basic Setup Menu
976-0043-01-02 B–5
Basic Setup Menu
Table B-2 provides a list of Basic Setup Menu headings and menu items,
with available set points. This table also provides the default settings for
each menu item as programmed in the factory. The last column “User
Settings” is provided for you to write in the settings specific to your
installation.
Table B-2
Basic Setup Default and User Settings for the Sine Wave Plus 2524 and 2548 Models
Sine Wave Plus 2524 Sine Wave Plus 2548
User
SettingsBasic Setup Menus
Range/
Display Default
Range/
Display Default
10 Time of Day Setup Menu See “10 Time of Day Setup Menu” on page 6–11 for details.
10A Set Hour 00:00:00 to
23:50:00
00:00:00 00:00:00 to
23:50:00
00:00:00
10B Set Minute 00:00:00 to
00:09:00
00:00:00 00:00:00 to
00:09:00
00:00:00
10C Set Second 00 to 59 00:00:00 00 to 59 00:00:00
11 Inverter Setup Menu See “11 Inverter Setup Menu” on page 6–12 for details.
11A High Battery Cut Out Vdc 16.1 to 34.0 32.0 32.2 to 68.0 64.0
11B Low Battery Cut In Vdc 16.1 to 33.9 26.0 32.2 to 67.8 52.0
11C Low Battery Cut Out Vdc 11.0 to 33.9 22.0 32.0 to 67.8 44.0
11D LBCO Delay Minutes 01 to 255 15 01 to 255 15
11E Search Watts (SRCH) 00 to 248 08 00 to 248 08
12 Battery Charging Menu See “12 Battery Charging Menu” on page 6–19 for details.
12A Finish Stage SILENT
FLOAT
FLOAT SILENT
FLOAT
FLOAT
12B Bulk Volts DC 20.0 to 32.0 28.8 40.0 to 64.0 57.6
12C Float Volts DC 20.0 to 32.0 26.8 40.0 to 64.0 53.6
12D Equalize Volts DC 20.0 to 32.0 28.8 40.0 to 64.0 57.6
12E Max Charge Amps AC 01 to 20 20 01 to 20 20
12F Bulk Done Amps AC 00 to 45 10 00 to 45 10
12G EQ Vdc Done Timer 00:00 to
23:50
02:00 00:00 to
23:50
02:00
12H Max Bulk/EQ Timer 00:00 to
23:50
05:00 00:00 to
23:50
05:00