Xantrex Technology SW Plus 4024 Power Supply User Manual


 
User Menu Description
976-0043-01-02 8–17
01D Bypass Mode
The Bypass Modecloses the internal bypass relays and allows the AC
connected to the selected input (AC1 or AC2) to pass directly through to
the loads without being monitored for AC voltage or frequency quality.
NORM When NORM is selected in the menu, the available inputs are
monitored for voltage and frequency.
AC1, AC2 If AC1 or AC2 is selected in this menu, the AC applied to
that input will not be monitored for voltage or frequency problems which
will pass directly through to the load, bypassing the inverter’s monitoring
circuits.
02 Generator ON/OFF Menu
The 02 Generator ON/OFF Menu is used for controlling a generator
equipped with remote start features and connected to the inverter by way
of the optional GSM. The generator can be manually switched ON or
OFF using the inverter control module or set to run automatically based
on programmed usage parameters. This menu heading also provides
generator status menus (02B through 02F) to help determine “why” a
generator started.
Important: All system functions are disabled in this mode and can only be
restored by selecting NORM. After returning to NORM, you must reselect your
user settings in the 01A Inverter menu item.
CAUTION: Damage to AC Loads
When Bypass Mode is selected, the Sine Wave Plus allows any AC power
supplied (utility or generator) to pass through the inverter to AC loads. If the
source of AC is not adequately regulated it can cause instability in voltage and
frequency which can damage connected AC loads. Xantrex does not recommend
use of Bypass Mode in areas of unstable AC power supply.
Note:
Auto-starting or controlling a generator with the inverter is only
possible with generators that have an electric starter and are compatible with
two- or three-wire external relay control. The optional GSM accessory is
required to perform automatic-generator starting operations.