Xantrex Technology SW Plus 4024 Power Supply User Manual


 
Menu Item Descriptions
976-0043-01-02 7–39
26F 15 Min Start Volts DC
This menu item sets the battery’s DC voltage level which initiates
automatic generator starting whenever the voltage drops below this
setting continuously for 15 minutes. This item is not temperature
compensated and is defeated during the quiet time period set in the
24 Generator Timers Menu.
26G Read LBCO 30 Sec Start
This menu item monitors the 11C Low Battery Cut Out VDC level and
initiates automatic generator starting whenever the voltage drops below
the LBCO setting continuously for 30 seconds. The LBCO setting is not
temperature compensated. This display is linked and adjusted in menu
11C Low Battery Cut Out VDC. The 30 second start attempts to
auto-start the generator even if the quiet time (as set in menu
24 Generator Timers Menu) is enabled. This is a read-only display.
27 Save/Restore Settings Menu
This menu provides the means to:
save recently programmed settings,
restore previously programmed settings, or
to restore factory default settings.
27A Push INV now to Save Settings
This menu item provides the means to save settings currently
programmed into the inverter.
To save settings:
1. When 27 Save/Restore Settings Menu is displayed, press the
button to select 27A Push INV Now to Save Settings.
2. Press the red INV button to save the settings.
Note: The settings in this menu are identical to Menu 14. Saving or restoring
settings at either menu will apply to all menu settings (Basic and Advanced).