Xantrex Technology SW Plus 4024 Power Supply User Manual


 
Advanced Setup
7–2 976-0043-01-02
Advanced Setup Summary
Check Defaults The following model-specific tables provide the default settings for the
Sine Wave Plus Advanced Setup Menu and cross-reference pages for
locating information on each menu item.
Table 7-1, “Advanced Setup Default Settings for the Sine Wave Plus
2524 and 2548 Models” on page 7–2
Table 7-2, “Advanced Setup Default Settings for the Sine Wave Plus
4024 and 4048 Models” on page 7–5
Table 7-3, “Advanced Setup Default Settings for the Sine Wave Plus
Plus 5548 Models” on page 7–7
Record Changes If your system requires changes to these default settings, record the
changes on the model-specific tables in Appendix B, “Configuration
Settings” before your start programming. These tables are found on the
following pages:
Table B-5, “Advanced Setup Default and User Settings for the Sine
Wave Plus 2524 and 2548 Models” on page B–10
Table B-6, “Advanced Setup Default and User Settings for the Sine
Wave Plus 4024 and 4048 Models” on page B–12
Table B-7, “Advanced Setup Default and User Settings for the Sine
Wave Plus 5548 Model” on page B–14
For directions on how to get to the Advanced Setup Menu, see
“Accessing the Advanced Setup Menu” on page 7–11.
Table 7-1
Advanced Setup Default Settings for the Sine Wave Plus 2524 and 2548 Models
Advanced Setup Menus
Sine Wave Plus 2524 Sine Wave Plus 2548
See PageRange/Display
Default
Settings Range/Display
Default
Settings
20 Silent Setup Menu See “20 Silent Setup Menu” on page 7–13 for details.
20A Refloat High Volts DC 16.1 to 33.9 28.4 32.2 to 67.8 56.8 page 7–15
20B Refloat Low Volts DC 16.1 to 33.8 25.0 32.2 to 67.8 50.0 page 7–15
20C Float Done Amps AC 00 to 40 10 00 to 40 10 page 7–15
20D Must Float Time Min 00 to 255 05 00 to 255 05 page 7–15
End Menu 20
21 Grid AC1 Usage Menu See “21 Grid (AC1) Usage Menu” on page 7–16 for details.
21A Grid Usage SB BX SB SB BX SB page 7–17
21B Grid Usage Begin h:m 00:00 to 23:50 21:00 00:00 to 23:50 21:00 page 7–17