Xantrex Technology SW Plus 4024 Power Supply User Manual


 
Inverter Specifications
A–2 976-0043-01-02
Electrical Specifications
AC Input Voltage (nominal) 120 Vac 120 Vac
AC Input Voltage Range 80 to 150 Vac 80 to 150 Vac
AC Input Current 60 amps AC Pass-
through/ 20 amps
AC Charging
60 amps AC Pass-
through/ 20 amps
AC Charging
AC1 Input Frequency Range 55 to 65 Hz 55 to 65 Hz
AC2 Input Frequency Range 54 to 67 Hz 54 to 67 Hz
Continuous Power (@ 25°C) 2500 VA 2500 VA
Efficiency (Peak) in inverter mode 95% 95%
Inverter Voltage (RMS) 120 Vac 120 Vac
Inverter Voltage Regulation ± 3% ± 3%
Frequency (Nominal ±0.04% Crystal
Controlled - Invert Mode)
60 Hz 60 Hz
Continuous Output (@25° C) 21 amps rms 21 amps rms
Surge Capability (@25° C)
5 second rating (resistive) 80 amps RMS 80 amps RMS
Over current trip point 125 amps Peak 175 amps Peak
Inverter Voltage THD
(Total Harmonic Distortion)
(Resistive Load)
< 5% < 5%
Automatic Transfer Relay 60 amps rms 60 amps rms
DC Input Voltage (Nominal) 25.2 Vdc 50.4 Vdc
DC Input Voltage Range 22 to 32 Vdc 44 to 64 Vdc
DC Current at Rated Power (Invert
Mode, Internal temp. stabilized)
120 amps DC 60 amps DC
Idle Consumption (Invert Mode/No
Load)
< 16 watts < 20 watts
Search Mode Consumption
(Default setting)
< 2 watts < 2 watts
Continuous Charge Rate
(at 120 Vac input)
70 amps DC 40 amps DC