Honeywell DCP552 Mark II Network Card User Manual


 
7-2
Modifying individual items and exiting the setting mode
Pressing the ENTER key while an individual item is displayed causes the set
value to flash and enables the registration state. At this point, the key and
key allow you to increase or decrease the values, while the key and key
move the digit positions on the display at which the values flash.
Pressing the ENTER key after the flashing number has been changed to the
desired value stops the flashing, the number reverts to the on state and the new
setting is stored in internal memory.
Modification of settings is terminated by pressing either the PARA key (valid for
variable parameters and event configuration data), PID key (valid for PID
parameters and constant value control data), SETUP key (valid for setup data) or
DISP key. Pressing the PARA key, PID key or SETUP key moves the cursor
to the next item stops the flashing and the number reverts to its normal on state.
Pressing the DISP key enables the normal display mode.
Should display panel 2 show “-----” during display of an individual item or
pressing the ENTER key not enable the registration state, it means that settings
cannot be made or modified for that item.
Handling Precautions
When PA01 is set to more than 1 in a variable parameter setting, PA03
and items beyond are not displayed. PA03 and items beyond cannot be
changed when PA02 is set to more than 1.
Event configuration data settings cannot be changed when PA02 is set
to a value more than 1. Also, when PA02 is set to 0 or 1, the event type
setting and some auxiliary settings (output points of code events) cannot
be changed.
PID parameter settings cannot be changed when PA02 is set to 4 or 5.
Setup data settings cannot be changed when PA02 is set to a value
more than 1 and cannot be displayed in modes other than the READY
mode.
The fixed control data setting cannot be changed when PA02 is set to 4
or 5. And, since the FUNC and PID keys are invalid in modes other than
the READY mode, a ConSt setting cannot be displayed or changed.