Honeywell DCP552 Mark II Network Card User Manual


 
12-15
Writing into EEPROM
(1) Press SETUP key until the PROG/SEG display shows (02-09).
(2) Scroll , , , , keys to show (1.1.1.1.) on upper display.
(3) Press ENTER key.
Current output calibration
Scroll , , , , keys to show (6.0.6.6.) on the upper display, then press
ENTER key.
Connect the digital ammeter across terminals (See Figure 12-9).
OUT CH1 output calibration
(1) Press SETUP key until the PROG/SEG display shows (06-01).
Scroll , , , , keys until meter indicates 4.00mA, then press ENTER
key.
(2) Press SETUP key until the PROG/SEG display shows (06-02).
Scroll , , , , keys until meter indicates 20.00mA, then press ENTER
key.
OUT CH2 output calibration
(1) Press SETUP key until the PROG/SEG display shows (06-03).
Scroll , , , , keys until meter indicates 4.00mA, then press ENTER
key.
(2) Press SETUP key until the PROG/SEG display shows (06-04).
Scroll , , , , keys until meter indicates 20.00mA, then press ENTER
key.
AUX CH1 output calibration
(1) Press SETUP key until the PROG/SEG display shows (06-05).
Scroll , , , , keys until meter indicates 4.00mA, then press ENTER
key.
(2) Press SETUP key until the PROG/SEG display shows (06-06).
Scroll , , , , keys until meter indicates 20.00mA, then press ENTER
key.
AUX CH2 output calibration
(1) Press SETUP key until the PROG/SEG display shows (06-07).
Scroll , , , , keys until meter indicates 4.00mA, then press ENTER
key.
(2) Press SETUP key until the PROG/SEG display shows (06-08).
Scroll , , , , keys until meter indicates 20.00mA, then press ENTER
key.
Chapter 12. CALIBRATION