DCP552 Parameter Work Sheet
Event Meaning Setting Operation Auxiliary settings
type category category
0 Event off ----- ----- Auxiliary 1 : None Auxiliary 2 : None
1 Time event Segment Time Auxiliary 1 : None Auxiliary 2 : None
2 PV upper limit Segment PV Auxiliary 1: Hysteresis Auxiliary 2 : None
3 PV lower limit
4 Deviation upper limit
5 Deviation lower limit
6
Deviation upper limit with standby
7
Deviation lower limit with standby
8
Absolute value deviation upper limit
9
Absolute value deviation lower limit
10
Absolute value deviation upper limit with standby
11
Absolute value deviation lower limit with standby
12 PV deviation rate upper limit Segment PV Auxiliary 1 : Sampling cycle Auxiliary 2 : None
13 PV deviation rate lower limit
14 SP upper limit Segment PV Auxiliary 1: Hysteresis Auxiliary 2 : None
15 SP lower limit
16 MV upper limit
17 MV lower limit
18 Code event Segment Code Auxiliary 1 : No. of output Auxiliary 2 : None
19
SOAK absolute value deviation upper limit
Segment PV Auxiliary 1: Hysteresis Auxiliary 2 : None
20
SOAK absolute value deviation lower limit
21
SOAK absolute value deviation upper limit with standby
22
SOAK absolute value deviation lower limit with standby
23 Code event with timer Segment Code time Auxiliary 1 : No. of output Auxiliary 2 : None
No. Item code Item
Factory default
User Settings and descriptions
settings
settings
34 E12-t Event 12 event type 0 0 to 253
35 E12-1 Event 12 auxiliary setting 1 ----- –19999 to +20000
(Setting range is variable according to the event types.)
36 E12-2 Event 12 auxiliary setting 2 ----- –19999 to +20000
(Setting range is variable according to the event types.)
37 E13-t Event 13 event type 0 0 to 253
38 E13-1 Event 13 auxiliary setting 1 ----- –19999 to +20000
(Setting range is variable according to the event types.)
39 E13-2 Event 13 auxiliary setting 2 ----- –19999 to +20000
(Setting range is variable according to the event types.)
40 E14-t Event 14 event type 0 0 to 253
41 E14-1 Event 14 auxiliary setting 1 ----- –19999 to +20000
(Setting range is variable according to the event types.)
42 E14-2 Event 14 auxiliary setting 2 ----- –19999 to +20000
(Setting range is variable according to the event types.)
43 E15-t Event 15 event type 0 0 to 253
44 E15-1 Event 15 auxiliary setting 1 ----- –19999 to +20000
(Setting range is variable according to the event types.)
45 E15-2 Event 15 auxiliary setting 2 ----- –19999 to +20000
(Setting range is variable according to the event types.)
46 E16-t Event 16 event type 0 0 to 253
47 E16-1 Event 16 auxiliary setting 1 ----- –19999 to +20000
(Setting range is variable according to the event types.)
48 E16-2 Event 16 auxiliary setting 2 ----- –19999 to +20000
(Setting range is variable according to the event types.)
● Event type