Honeywell DCP552 Mark II Network Card User Manual


 
2 - 3 Input Type and Range Number
2-8
Input
Thermocouple
Resistance temperature detector (RTD)
Chapter 2. NAMES AND FUNCTIONS OF PARTS
Input type
Symbol
Code
Accuracy (under standard conditions)
±0.1%FS
±0.3%FS at -200 to -45 ˚C
±4.0%FS at 0 to 260 ˚C, 
±0.15%FS at 260 to 800 ˚C
±0.9%FS at 0 to 300 ˚C, 
±0.5%FS at 300 to 800 ˚C
Input range (FS)
˚C
Range No.
˚F
K (CA) K46
-200.0 to +200.016
-300.0 to +400.0
±0.1%FSK (CA) K09
0.0 to 1200.000 to 2400
±0.1%FSK (CA) K08
0.0 to 800.010 to 1600
±0.1%FSK (CA) K04
0.0 to 400.020 to 750
±0.1%FSE (CRC) E08
0.0 to 800.030 to 1800
±0.1%FSJ (IC) J08
0.0 to 800.040 to 1600
±0.1%FST (CC) T44
-200.0 to +300.05 -300 to +700
±0.1%FSB (PR30-6) B18
0.0 to 1800.060 to 3300
±0.1%FSR (RR13) R16
0.0 to 1600.070 to 3100
±0.1%FSS (PR10) S16
0.0 to 1600.080 to 3100
±0.1%FSW (WRe5-26) W23
0.0 to 2300.090 to 4200
±0.1%FSW (WRe5-26) W14
0.0 to 1400.010 0 to 2552
±0.2%FSPR40-20 D19
0.0 to 1900.011 0 to 3400
±0.1%FSN U13
0.0 to 1300.012 32 to 2372
±0.1%FSPL II Y13
0.0 to 1300.013 32 to 2372
±0.1%FSNi-Ni • Mo Z13
0.0 to 1300.014 32 to 2372
±0.4%FS
Gold, iron, chromel
Z06
0.0 to 300.0K (K : Kelvin)15