12-12
PV zero, span
(1) PV zero adjustment
(a) Press SETUP key until the PROG/SEG display shows (01-03).
(b) Adjust your calibration device to an output signal equal to the 0% range
value (See Table 12-9), the signal need to be on the input for 10 to 15
seconds.
(c) Press ENTER key after display stabilizes.
(2) PV span adjustment
(a) Press SETUP key until the PROG/SEG display shows (01-04).
(b) Adjust your calibration device to an output signal equal to the 100% range
value (See Table 12-9).
(c) Press ENTER key after display stabilizes.
Table 12-9.
Writing into EEPROM
Press SETUP key until the PROG/SEG display shows (01-05).
Scroll , , , , keys to show (1.1.1.1.) on the upper display.
Press ENTER key.
Chapter 12. CALIBRATION