Honeywell DCP552 Mark II Network Card User Manual


 
19
DCP552 Parameter Work Sheet
No. Item code Item
Factory default
User Settings and descriptions
settings
settings
1 ConSt Control mode 0 0 : Program run mode
1:Fixed command control mode
2 SP Set point 0 Within setup C66 to C67 setting (SP limit)
3 P Proportional band 100.0 0.0 to 1000.0%
(0.0 : On-off control)
4 I Integral time 0 0 to 3600sec
(0: no integral operation)
5 d Derivative time 0 0 to 1200sec
(0: no derivative operation)
6 rE Manual reset 50.0 0.0 to 100.0%
7 oL
Manipulated variable lower limit
0.0 –5.0 to upper limit %
8 oH
Manipulated variable upper limit
100.0 Lower limit to +105.0%
Fixed command control data (CH1) setting
No. Item code Item
Factory default
User Settings and descriptions
settings
settings
1 ConSt Control mode 0 0 : Program run mode
1:Fixed command control mode
2 SP Set point 0 Within setup C69 to C70 setting (SP limit)
3 P Proportional band 100.0 0.0 to 1000.0%
(0.0 : On-off control)
4 I Integral time 0 0 to 3600sec
(0: no integral operation)
5 d Derivative time 0 0 to 1200sec
(0: no derivative operation)
6 rE Manual reset 50.0 0.0 to 100.0%
7 oL
Manipulated variable lower limit
0.0 –5.0 to upper limit %
8 oH
Manipulated variable upper limit
100.0 Lower limit to +105.0%
Fixed command control data (CH2) setting