8-16
■ Setting PV start items
(1) In the set value display state, move to the PV start item to be set for the
segment on the programming map.
(A PV start item is a program setting and is the same for each segment.)
(2) Press the ENTER key to make display panel 2 flash (registration of first
setting).
(3) Use the ↑, ↓, ←, and → keys to make the first setting – setting the PV start
value.
Setting range:0 to 3
0: no PV start
1: descending PV start
2: ascending PV start
3: bi-directional PV start
(4) Press the ENTER key to stop the flashing on display panel 2.
(Pressing the FUNC and CLR keys causes display panel 2 to return to unset
state “0 ” and the flashing stops.)
● Display
• A PV start item is a program setting and is the same for each segment.
• When setup data C60 is set to 1, a PV start item on the programming map is
skipped and not displayed.
NOTE
A PV start item setting does not use subfunctions.