DCP552 Parameter Work Sheet
No. Item code Item
Factory default
User Settings and descriptions
settings
settings
34 C 34 Manipulated variable in PV 0.0 –5.0 to +105.0%
overrange (CH1)
35 C 35 MANUAL change mode (CH1) 0 0 : Smooth
1:Preset
36 C 36 Preset MANUAL value (CH1) 0.0 –5.0 to +105.0%
37 C 37 End of operation (CH2) 0 0 : READY mode
1:END mode
38 C 38 Manipulated variable in READY 0.0 -5.0 to +105.0%
mode (CH2)
39 C 39 Manipulated variable setting in 0 0 : No
PV overrange (CH2) 1 : Yes
40 C 40 Manipulated variable in PV 0.0 -5.0 to +105.0%
overrange (CH2)
41 C 41 Manual change mode (CH2) 0 0 : smooth
1:preset
42 C 42 Preset MANUAL value (CH2) 0.0 -5.0 to +105.0%
43 C 43 Service interruption time when 0 0 to 3600sec
running can be continued
44 C 44 CP computation type 1 0 : oxygen pressure (PO
2) computation
1:CP computation for NKG sensor
2:CP computation for Marathon monitors and Cambridge
sensors
3:CP computation for Corning sensors
4:CP computation for AACC sensors
5:CP computation for Barber-Coleman sensors
6:CP computation for Furnace Control sensors
45 C 45 Auxiliary output 1 type 0 0 : SP1
1:PV1
2:Deviation1 (DEV1)
3:Manipulated variable 1 (MV1)
4:SP2
5:PV2
6:Deviation 2 (DEV2)
7:Manipulated variable 2 (MV2)
8:O2 sensor mV input value
46 C 46
Auxiliary output 1 lower limit (4mA)
0 SPU –19999 to +20000 SPU (C45 not equal to 3)
–1999.9 to +2000.0% (C45 set to 3)
47 C 47
Auxiliary output 1 upper limit (20mA)
10000 SPU –19999 to +20000 SPU (C45 not equal to 3)
–1999.9 to +2000.0% (C45 set to 3)
48 C 48 Auxiliary output 2 type 0 0 : SP1
1:PV1
2:Deviation1 (DEV1)
3:Manipulated variable 1 (MV1)
4:SP2
5:PV2
6:Deviation 2 (DEV2)
7:Manipulated variable 2 (MV2)
8:O2 sensor mV input value
49 C 49
Auxiliary output 2 lower limit (4mA)
0 SPU –19999 to +20000 SPU (C48 not equal to 3)
–1999.9 to +2000.0% (C48 set to 3)
50 C 50
Auxiliary output 2 upper limit (20mA)
10000 SPU –19999 to +20000 SPU (C48 not equal to 3)
–1999.9 to +2000.0% (C48 set to 3)
57 C 57 Programming item 0 0: Displayed
Event 1 : Not displayed
58 C 58 Programming item 0 0: Displayed
PID group, output limiter group 1: Not displayed
59 C 59 Programming item 0 0: Displayed
G.SOAK, PV shift, repeat 1 : Not displayed
60 C 60 Programming item 0 0: Displayed
PV start, cycle, pattern link 1 : Not displayed
denotes items settable only on models with CP compensation