Honeywell DCP552 Mark II Network Card User Manual


 
5-21
Cycle
Separate cycles can be set in CH1 and CH2 programs.
The cycle function allows you to repeat operation from segment 1 to the last
segment in a program pattern the number of times set in the cycle count. A total of
10,000 times can be set.
When a cycle number of n is set, the total operation count is n + 1. During cycle
operation, the operation at the last point in the final segment is not performed and
executed values of program items (sequels to settings in the previous segment ; for
example, PV event value, pid group number) that continue from a previous
segment are cleared before program restart.
When the SP start point and end point are not equal, SP changes in a step-like
manner during cycle operation.
Chapter 5. FUNCTIONS
Cycle 1
SP
Time
(1)
(2)
(3)
(4)
(5)
(6)