12 - 2 Calibration Procedures
■ Enter calibration mode
(1) Release keylock. (PARA PA01=0)
(2) Press DISP key to permit ordinary indication condition.
Change to READY (RUN and HLD are off) and AUTO (MAN off) modes.
The following LEDs will illuminate after the above operations.
RUN LED is OFF
HLD LED is OFF
MAN LED is OFF
Figure 12-2.
(3) To enter calibration mode, hold down the FUNC key, and press SETUP key
and ENTER key simultaneously.
The display will show the symbols described in Figure 12-3. If the indication
is different, repeat the above procedure after pushing DISP key to refresh the
display.
(4) To select individual calibration items, press ↑, ↓, ←, →, keys to select the
item by scrolling, then SETUP key, and ENTER key.
The order of calibration items is described in Table 12-2.
Figure 12-3.
0.0.0.0.
A.d.J.S.
00 00
12-7
Chapter 12. CALIBRATION