12-10
● Digital output test for control output (00-04)
Press SETUP key until the PROG/SEG display shows (00-04).
When the digit of upper display is changed by ↑, ↓, ←, →, keys, the state of 6D
or 8D control output is changed as shown in Table 12-6.
Since the 6D hardware is of current output (8D hardware is of open collector)
specification, the ON/OFF check must be performed in meeting with the
specification.
Table 12-6.
● Digital output test for event (00-05)
Press SETUP key until the PROG/SEG display shows (00-05).
Table 12-7. DO
0.0.0.0.
0.0.0.1.
0.0.0.2.
0.0.0.4.
0.0.0.8.
0.0.1.0.
0.0.2.0.
0.0.4.0.
0.0.8.0.
0.1.0.0.
0.2.0.0.
0.4.0.0.
0.8.0.0.
1.0.0.0.
2.0.0.0.
4.0.0.0.
8.0.0.0.
↕ ↕ ↕ ↕ ↕ ↕ ↕ ↕ ↕ ↕ ↕ ↕ ↕ ↕ ↕ ↕
0.0.0.0.
0.0.0.1.
0.0.0.2.
0.0.0.4.
0.0.0.8.
Chapter 12. CALIBRATION