8-5
■ Display items
Items displayed are shown in the figure below.
■ Setting pattern items
(1) In the set value display state, move to the segment pattern item to be set on the
programming map.
(2) Press the ENTER key to make display panel 1 flash (registration of first
setting).
(3) Use the ↑, ↓, ←, and → keys to set the first setting (SP).
Setting range: SP limit lower limit to upper limit
(SP limit is set using setup data C66, C67, C69 and C70.)
(4) Pressing the ENTER key stops display panel 1 from flashing and causes
display panel 2 to start flashing. (This starts start registration of the second
setting.) Instead of pressing the ENTER key, press the FUNC and ENTER
keys to switch between RAMP types (selecting RAMP-X ⇔ RAMP-T, or
RAMP-X ⇔ RAMP-E is made with setup data C61).
(5) Use the ↑, ↓, ←, and → keys to make the second setting (time).
Setting range: 0:00 to 500:00, 0.0 to 3000.0
(Time units are selected using setup data C62 to set Hour/min, Min/sec, 0.1
sec. Since a colon “: ” cannot be displayed, the decimal point is used instead.)
(6) Press the ENTER key to stop display panel 2 from flashing.
Chapter 8. PROGRAM SETUP