FR Configurator Setting [Setting]
* When connecting with FA transparent function, set the time-out value in 500ms increments (Example: 500 / 1000 / 1500 /... / 30000).
2.6.3 Environmental Setting
You can specify the place for saving data (directory) and default system.
H
Interrogate Time 1 Sets an interval for sending data (display and error check of the operation mode) to the inverter.
The value must be set 2s shorter than the communication check time interval (Pr.122, Pr.336 or
Pr.548). If it is set longer than the setting value of communication check time interval (Pr.122, Pr.
366 or Pr. 548), the inverter will come to an alarm stop.
I
Time Out* 1000 Sets the time for a personal computer to receive a response from an inverter after sending a data
to the inverter from the personal computer. If there is no response after the set time is passed,
"Time out" error will be displayed.
J
[OK] button Recognizes the setting value on the communication screen and returns to the system setting
screen.
K
[Cancel] button Cancels the communication settings and returns to the system setting screen.
L
[Reflect Default] button Used to omit the setting of the values specified in communication settings from the next time
onward.
M
[Default Read] button
Used to read the default values. The value is as set with the [Reflect Default] button.
N
[Initial Value] button Used to return the communication setting to the initial value.
O
GOT Transparent
communication
Check when using FA transparent function.
CAUTION
When using FA transparent communication, communication error (Time Out) may occur when FR Configurator starts communication during Time
Out occurrence in GOT (when GOT is monitoring the inverter which is not connected).
In that case, set the Time Out value more than the following.
Time Out value of GOT[s] x (Retry count of GOT + 1) x 3 x1000[ms] (500ms increments)
If the value above is more than 30[s], make adjustment to "Time Out value" and "Retry count" of GOT so that the value above is less than 30[s].
No. Name
Function and description
A
Default Data Directory
Set the folder (directory) displayed first in a data saving screen, "Save with file name", or a
opening file screen,"Open file".
Once the data is saved in a different folder, the same folder where the data is saved and opened
will be displayed when saving the data again.
B
System block read is done at start-up
Turn on the check box to execute automatically [System Read] when starting of FR Configurator. If
the default system file is registered, system block read is not performed automatically at the
startup.
C
When the parameter is read it is
distinguished automatically
Turn on the check box to hide the parameters read-disabled for parameter batch-read or batch-
verify from the error panel. (Refer to page 29)
D
Default Sys File
Registers the system file (*.MEL) which is automatically opened when starting FR Configurator. If
the default system file is registered, system block read is not performed automatically at the
startup.
There is no default system file registered at the installation.
No. Name
Function and description
Initial
value
CAUTION
If the value of Interrogate Time is set shorter, the menu or buttons of each window may
be slow to respond depending on operating model and communication speed.
A
B
C
D