Parameter Setting [Parameter]
(1) FM/CA/AM calibration
The full scale of terminal FM/CA, terminal AM can be calibrated.
The dedicated adjustment screen is used for terminal FM/CA/AM calibration (Pr. 900, Pr. 901).
Press the [Click] button in the parameter list to show the FM/CA/AM terminal adjustment panel.
FM/CA/AM calibration is enabled during the ONLINE mode only.
<Calibration method>
1) Set to the ONLINE mode.
2) Set the monitor with using Pr. 54 FM/CA terminal function selection (Pr. 158 AM terminal function selection).
3) Press the [Click] button in Pr. 900/Pr. 901 row to show the FM/CA/AM terminal adjustment panel.
4) Input the running frequency in the full-scale state, and press [Selected].
5) Press [FWD]/[REV] to start the inverter.
6) Calibrate the scale of the meter in the full-scale state with the / button.
7) Press [Fin.[Stop]] button after adjustment to write the calibration value to the inverter.
To cancel the calibration, press the [Cancel] button.