![](http://pdfasset.owneriq.net/5/15/515f269a-2b9a-440f-ac51-b1891a3eeee6/515f269a-2b9a-440f-ac51-b1891a3eeee6-bg2f.png)
Installing the ANH-8/DC
312410-A Rev 00
2-5
Verifying Site Requirements
Verify that your installation meet the requirements listed in this section.
• Space Requirements
• Electrical Requirements
• Environmental Requirements
Space Requirements
The installation site must provide a certain amount of free space around the
ANH-8/DC to dissipate heat. Install the ANH-8/DC in a space that meets these
specifications:
• Width: 19.25 in. (48.9 cm)
• Minimum depth: 17.25 in. (43.8 cm)
• Depth for servicing: 26.25 in. (66.7 cm)
Electrical Requirements
The installation site must provide an isolated power source that meets these
electrical specifications:
• Input voltage of -48.0 or -60.0 volts DC
• 1.5 amperes (A) input current under full load at -38.0 VDC input
• Reinforced insulation from the main AC power
We recommend the use of #16 AWG cables between the AN/DC and the power
source to minimize voltage drop. When measuring the cable run, be certain to
include both the input and return cables.
Note:
The AN/DC should be installed only in dedicated equipment rooms
where access is limited to qualified service personnel.